
PROPERTY OF SOLIDSTATE CONTROLS, INC. 7/1998
supply this transformer mounted in a matching cabinet, if desired, or can supply a standard
transformer of another manufacturer in their own floor-mounted enclosure. Some customers may
wish to have their own electrical contractor supply and install this along with other necessary
equipment.
The customer’s existing distribution panels, which previously supplied the computer loads, should
be re-evaluated before utilizing with the UPS. The inverter portion of the UPS can deliver only a
small amount of current above its nameplate ratting before the output voltage drops off drastically.
Consequently, the current available to trip the distribution breakers is severely limited. Ideally
breakers and/or fuses should be selected to clear the possible faults without overloading the
inverter. When overloads do occur, the static switch will transfer all loads to the bypass (utility)
source without interruption, where the large capacity will clear the fault. Since all transfers involve
some risk to the load, all unnecessary transfers should be avoided.
For further information regarding fault protection, please refer to “UPS Systems Distributor Network
Protection” by Laura Andrei, R & D Engineer.
An Uninterruptible Power System (UPS) is the most complete form of power conditioning available.
A UPS can provide complete protection from all forms of line voltage transients, surges and sages,
long duration brown outs, and is the only device which can provide total ‘no break’ back-up
protection against black outs.
It is commonly recognized that the various voltage related problems that trouble your computer
come from two sources. The first is atmospheric and accounts for approximately 20% of the total
power problems. The remaining 80% occurs within the users own building. This is a result of a
variety of conditions such as the presence of noise generating equipment like contactors, relays,
switches and fluorescent lighting, a general high power demand and the present of high inrush
loads like motors and other large inductors. Power problems also occur in the AC distribution
system as a result of distribution breakers with dirty contacts which result in high impedance, poor
connections including ground connections, incorrect grounding practices, improperly sized ground
neutral and power conductors and wiring errors. Surprisingly, wiring errors such as ground-neutral
reversals, poor or loose connections and improper wire sizes occur frequently, even in systems
which have been in use for a long period of time, and are unknowingly causing computer room
problems.
The UPS can correct all voltage problems caused by the various previously mentioned conditions
which exist up to the point of input to the UPS itself. However, if the AC distribution system which
exists between the output of the UPS and the various computer loads and peripherals has any of
the previously mentioned problems, voltage fluctuations may be re-introduced onto the clean
power generated by the UPS and, as a result, trouble with the computer system may continue. It is,
therefore, to the user’s benefit to be sure that this AC distribution system is designed and operating
properly. One would be cautioned not to assume that your AC distribution is error free, but that it be
properly analyzed by experts in that field.
Many such AC distribution systems have been designed by experts and have AC verifications
performed periodically (at least one a year) to assure that everything is operating properly, that
vibration has not loosened any connections, that circuit breakers have clean low impedance
contacts, that no loads have been added improperly and that breaker and wire current ratings have
Comentários a estes Manuais